PULS

Manufacturers

Viewed products

New products

PULS ML70.100 power supply 24 V

ML70100

Used

PULS ML70.100 DIN rail power supply 24 V DC 3 A, 72 W.

More details

Price on request

or call +47 908 92 500

Data sheet

Manufacturer PULS
Model MiniLine ML70.100
Manufacturers part number ML70.100
kW 0.072 kW (72 W)
Class Type approved: GL
Other Efficiency typ. 89 %, losses 8.7 W; hold-up over 40 ms @ 230 V; ripple below 50 mVpp; OVP below 40 V; internal fuse T3.15 A; green LED; PULS Overload Design
Weight 260 g
Amps Input 1.6 A @ 100 V AC / 0.8 A @ 220 V AC / 0.3 A DC; output 3 A @ 24 V, 2.6 A @ 28 V; overload up to 1.5 × rated
Volt Input 100–120 / 220–240 V AC (manual select), 47–63 Hz, or 290 V DC (−25 % / +30 %); output 24–28 V DC adjustable, set 24.5 V
Endurance MTBF approx. 600 000 h (SN 29500, 24 V / 3 A, 230 V AC, +40 °C)
Connection / terminals Spring clamp terminals, 2 per output; 0.3–2.5 mm² flexible / 0.3–4 mm² solid (28–12 AWG), strip 6 mm
Mounting DIN rail TS35/7.5 or TS35/15, snap-on; 25 mm free space at ventilated sides
Standards / approvals Label: GL, cULus listed E137006, NEC Class 2, CSA, Class I Div 2 T4 A–D, CE. Data sheet: EN 60950, EN 50178, UL 508, CB Scheme, SELV/PELV, IP20
Working temperature max, celsius degrees Operation −10 °C to +60 °C (label), up to +70 °C with derating (data sheet); storage −25 °C to +85 °C
DIMENSIONs 45 × 75 × 91 mm (W × H × D, + DIN rail)

More info

PULS MiniLine ML70.100 single-phase DIN rail power supply. Designed in Germany, assembled in China.

  • Input 100–120 / 220–240 V AC (manual selector), 1.6–0.8 A, 50–60 Hz; or 290 V DC (−25 % / +30 %), 0.3 A
  • Output 24–28 V DC adjustable, 3–2.6 A, factory set 24.5 V; max. 72 W; DC OK LED
  • Operating temperature −10 °C to +60 °C
  • Approvals: GL, cULus listed (IND. CONT. EQ., E137006), NEC Class 2, CSA, Class I Div 2 T4 groups A–D, CE

Data sheet values (PULS ML70.100, rev. December 2004)

  • Input AC 100–120 / 220–240 V selectable by switch, 47–63 Hz, also DC 220–375 V; internal fuse, no external fusing needed
  • Output DC 24–28 V adjustable on front (preset 24.5 V), 3 A at 24 V, 72 W; no switch-off on overload – delivers up to 1.5 × rated current
  • Efficiency typ. 89 %, hold-up time over 40 ms at 230 V AC, MTBF approx. 600 000 h
  • Operation −10 °C to +70 °C with derating; IP20, 45 × 75 × 91 mm, 260 g
  • UL 508 listed, CSA, CB Scheme, NEC Class 2, SELV / PELV